Pump duty point

The flow (Q) and pressure (P) the fire pump must deliver to satisfy the most demanding sprinkler design.

Definition

Selected from the manufacturer's pump curve at 100% flow; verified at 150% flow (pressure ≥ 65% of rated) and at churn (≤ 140% of rated) per EN 12845 §10 and NFPA 20 §4.7. Diesel pump sets require an automatic test routine every 4 weeks.