Design parameters
| Standard | NFPA 13 |
| Hazard class | Light Hazard |
| Design density | 0.10 gpm/ft² over 1500 ft² |
| Area of operation | 139 m² |
Design notes
- Quick-response heads throughout patient areas
- Coordinate with medical gas, MRI and isolation room constraints
- Dual electric + diesel pump set for resilience
- Smoke compartments aligned with sprinkler zones
Typical equipment
- QR concealed pendent K80
- Diesel + electric pump set
- Dual water supply
- Floor isolation valves per ward