EN 12845 · OH1 (Ordinary Hazard Group 1)

Hotel fire sprinkler design

Guest rooms, corridors and back-of-house in hotels are classified OH1 under EN 12845. NFPA 13 maps the same occupancy to Light Hazard with quick-response heads.

Design parameters

StandardEN 12845
Hazard classOH1 (Ordinary Hazard Group 1)
Design density5.0 mm/min
Area of operation72 m² (wet)

Design notes

  • Concealed pendent heads in guest rooms for aesthetics
  • Sidewall heads above bed lines where ceiling penetration is limited
  • Risers in service shafts with floor-level isolation valves
  • Coordinate with smoke control / pressurisation system

Typical equipment

  • QR pendent K80 sprinklers
  • Recessed concealed heads
  • DN100 wet alarm valve
  • Single electric pump