Design parameters
| Standard | EN 12845 |
| Hazard class | OH2–OH3 |
| Design density | 5.0–7.5 mm/min |
| Area of operation | 144 m² |
Design notes
- Stockrooms commonly drive the most onerous design area
- Separate dry system for unheated loading docks
- Coordinate with retail tenant fit-out guides
- Public-facing heads should be concealed or chrome-finished
Typical equipment
- Upright + concealed pendent K80/K115
- Dry pipe valve for loading dock
- Electric pump set
- Hydrant ring 4 bar