Recommended density 10 mm/min over each bay footprint. One K115 nozzle per ~9 m² at 1.0 bar.
Result
- Total protected area
- 104 m²
- Open deluge nozzles
- 12
- Suggested flow @ 1.0 bar (K115)
- 1380 L/min
Formula: N = ceil(bays · bay_area / coverage)