All tools
Tool · Hydraulics

Hydraulic mini-calculator

Quick pump duty estimate using EN 12845 design density and Hazen-Williams friction. For final design, run a full network calculation.

Design flow
720 L/min
Pump flow (+10%)
793 L/min
Total pump head
21.3 m
2.09 bar
Pipe friction
2.5 m
DN100, C=120
Head breakdown
  • Pressure at sprinkler: 5.7 m
  • Pipe friction loss: 2.5 m
  • Static lift: 8 m
  • Safety margin (0.5 bar): 5.1 m

Need to save these results, attach a 3D layout and export a stamped PDF report?