What deluge is
A deluge system uses open (no fusible link) sprinklers or spray nozzles. All heads in the zone discharge simultaneously when the deluge valve opens, triggered by a separate detection system.
EV parking application
Lithium-ion battery fires need huge cooling water flow to prevent thermal runaway propagation. FM DS 5-33 and emerging NFPA 88A guidance specify density ≥ 10 mm/min over the bay footprint. Deluge with side-by-side spray nozzles is the dominant approach.
Transformer protection
Oil-filled transformers use directional water-spray nozzles per NFPA 15. Densities range 6.1–10.2 L/min/m² of transformer surface. Drainage and oil separation are equally important to the deluge itself.
Flammable liquids
Foam-water deluge — combines deluge with proportioned foam concentrate. NFPA 11 + 16 govern. Application density is hazard-specific (typically 6.5 L/min/m² for hydrocarbon, 9.8 L/min/m² for polar solvents).