Home
NFPA 20

Fire pump test curve (churn / rated / 150%)

Required pump curve characteristics at three test points per NFPA 20.

Test pointFlowMin total head
Churn (shutoff)0%≤ 140% of rated
Rated100%100% of rated
Overload150%≥ 65% of rated

Uwagi

  • Annual flow test must reproduce the original certified curve within tolerance.
  • Diesel pumps tested at 100% rated speed.

Źródło

NFPA 20 (2022) §14.2.