Maximum area per sprinkler and maximum spacing between heads, by hazard.

HazardMax area per head (m²)Max spacing (m)Min spacing (m)
LH214.62
OH1242
HHP / HHS93.72
NFPA 13 Light QR18.64.61.8
NFPA 13 Ordinary12.14.61.8
NFPA 13 Extra (Ext. Coverage)37.27.32.4
ESFR9.33.72.4

Bron

EN 12845:2015 §12; NFPA 13 (2022) §10.2.4.