Indicative flow and pressure duty points for sizing fire pumps per EN 12845 hazard class.

HazardTypical flow (L/min)Typical pressure (bar)Pump type
LH375–7252.2–3.5Single electric
OH1540–7251.0–2.2Single electric
OH2725–11001.5–2.5Single electric or 2×100%
OH31100–18002.0–3.02×100% electric
HHP11750–24002.5–4.0Electric + diesel
HHP2–HHP42200–35003.0–5.0Electric + diesel
HHS3 / HHS42900–60004.0–7.5Electric + diesel, large

Opmerkingen

  • Excludes hose reels and external hydrant ring demand.

Bron

EN 12845:2015 §10; common engineering practice.