Home
NFPA 13

ESFR minimum design pressures by storage height

Minimum operating pressure at the most remote 12 sprinklers for ESFR protection of cartoned unexpanded plastics.

K-factor (US)Storage height (ft)Ceiling height max (ft)Min pressure (psi)
14253050
16.8253035
16.8354060
22.4354040
22.4404552
25.2404535
25.2434840

Opmerkingen

  • Cartoned unexpanded plastics — Group A. Different commodity classes require recalculation.

Bron

NFPA 13 (2022) Table 23.3.1.