Detector spacing (heat, smoke, beam)

Maximum spacing between detectors for smooth, level ceilings (no air movement adjustments).

Detector typeMax spacingMax area covered
Spot heat detector9.1 m (30 ft)84 m² (900 ft²)
Spot smoke detector9.1 m (30 ft)84 m² (900 ft²) per NFPA, 60 m² per EN 54-14
Beam smoke (4.6–7.6 m)18.3 m (60 ft) parallel beamsPer coverage width
Linear heat cable9.1 m (30 ft)Per linear m
VESDA / aspirating Class APer pipe layout≤ 2000 m² per sampling pipe

Bron

NFPA 72 (2022) Chapter 17; EN 54-14:2018.