Home
suppression

Water mist systems (low / intermediate / high pressure)

Water mist physics, classification by pressure, typical applications and standards (NFPA 750, EN 14972).

Extinguishing mechanism

Water mist suppresses fire by three combined mechanisms: heat absorption (vaporisation), oxygen displacement (steam expansion 1:1700), and radiant heat blocking. Droplets Dv99 ≤ 1000 µm (per NFPA 750 Class 3) or ≤ 200 µm (Class 1).

Pressure classes

Low pressure < 12 bar: simple piping, large droplets, similar to fine-spray sprinklers. Intermediate 12–34 bar: improved penetration. High pressure ≥ 35 bar (often 70–140 bar): small droplets, deepest penetration; needs stainless tubing.

Best applications

Marine machinery spaces (IMO MSC.1/Circ.1387), historic buildings (low water damage), turbines and combustion engines, road tunnels, kitchen hoods (UL 300A).

Limitations

Water-mist systems are typically zone-specific and require full-scale fire test data per the enclosure. Not a drop-in replacement for sprinklers in storage occupancies.

Quellen

  • NFPA 750 (2023)
  • EN 14972-1 (2020)
  • IMO MSC/Circ.1165