Home
EN 12845 / NFPA 13

Required water-supply duration by hazard

Minimum duration of water supply for sprinkler systems.

StandardHazardDuration (min)
EN 12845LH30
EN 12845OH (all)60
EN 12845HHP / HHS90
NFPA 13Light30
NFPA 13Ordinary60
NFPA 13Extra / Storage90
NFPA 13ESFR storage60

Source

EN 12845:2015 §9.2; NFPA 13 (2022) Table 19.3.3.1.1.

Cite this page
APA
FireTwin AI (2026). Required water-supply duration by hazard. FireTwin AI. https://firetwin.eu/data/water-supply-duration
IEEE
FireTwin AI, "Required water-supply duration by hazard," FireTwin AI, 2026. [Online]. Available: https://firetwin.eu/data/water-supply-duration