Home
NFPA 291

Hydrant residual pressure projection

Project residual pressure at a target flow from a 2-point hydrant flow test.

Uses the N^1.85 relationship: (P_s − P_target) = (Q_target/Q_test)^1.85 · (P_s − P_residual).

Result
Projected residual at target flow
0.61 bar
Projected residual
8.9 psi
Sufficient (≥ 1.4 bar)?
No ✗ — supply marginal

Formula: P_target = P_s − (Q_t/Q_r)^1.85 · (P_s − P_r)

Reference: NFPA 291

Embed this calculator

Paste into any blog post or documentation page. Free, no signup, links back to FireTwin AI.

<iframe src="https://www.firetwin.eu/embed/calc/hydrant-residual" width="100%" height="640" style="border:1px solid #e5e7eb;border-radius:8px" loading="lazy" title="Hydrant residual pressure projection — FireTwin AI"></iframe>